United States · design temperature
Heat pump sizing in Charlotte, NC
−3 °C(26 °F) design temperature
Design temperature used for Charlotte, NC: -3 °C (26 °F) — the 99 % annual heating design temperature, from 10 years of reanalysis weather. Treat it as ±1 °C: your street can be colder or milder than the grid cell.
What that means for load
Design heat load = your home's heat-loss coefficient (UA) × (70 °F − 26 °F). Illustrative only — your own UA is what matters, and a contractor's quote is often sized from a rule of thumb instead:
| UA (BTU/h·°F) | Design load (BTU/h) | ≈ tons |
|---|---|---|
| 200 | 8,784 | 0.7 |
| 300 | 13,176 | 1.1 |
| 400 | 17,568 | 1.5 |
| 500 | 21,960 | 1.8 |
Measure yours
Temsor RightSize reads 12–24 months of your utility bills, fits your real UA with an uncertainty range, and checks the heat pump you were quoted against real cold-climate capacity data. Try the free calculator.
Nearby cities
- Winston-Salem, NC (-4 °C design)
- Greensboro, NC (-4 °C design)
- Columbia, SC (-1 °C design)
- Raleigh, NC (-4 °C design)
Engineering estimate, not a stamped Manual J / permit document. Method validated on simulated homes. See the disclaimer.