Canada · design temperature
Heat pump sizing in Hamilton, ON
−20 °C(-4 °F) design temperature
Design temperature used for Hamilton, ON: -20 °C (-4 °F) — an estimate of the NBC 2.5 % January design temperature, from 10 years of reanalysis weather. Treat it as ±2 °C: your street can be colder or milder than the grid cell.
Recent winters (2015–2024) gave -17 °C (1 °F); the code value is an estimate of the NBC 1982–2006 figure (2.6 °C colder). Use your local code value if your contractor printed it.
What that means for load
Design heat load = your home's heat-loss coefficient (UA) × (70 °F − -4 °F). Illustrative only — your own UA is what matters, and a contractor's quote is often sized from a rule of thumb instead:
| UA (BTU/h·°F) | Design load (BTU/h) | ≈ tons |
|---|---|---|
| 200 | 14,742 | 1.2 |
| 300 | 22,113 | 1.8 |
| 400 | 29,484 | 2.5 |
| 500 | 36,855 | 3.1 |
Measure yours
Temsor RightSize reads 12–24 months of your utility bills, fits your real UA with an uncertainty range, and checks the heat pump you were quoted against real cold-climate capacity data. Try the free calculator.
Nearby cities
- Toronto, ON (-15 °C design)
- London, ON (-17 °C design)
- Windsor, ON (-16 °C design)
- Kingston, ON (-19 °C design)
Engineering estimate, not a stamped Manual J / permit document. Method validated on simulated homes. See the disclaimer.