United States · design temperature
Heat pump sizing in Indianapolis, IN
−13 °C(9 °F) design temperature
Design temperature used for Indianapolis, IN: -13 °C (9 °F) — the 99 % annual heating design temperature, from 10 years of reanalysis weather. Treat it as ±1 °C: your street can be colder or milder than the grid cell.
What that means for load
Design heat load = your home's heat-loss coefficient (UA) × (70 °F − 9 °F). Illustrative only — your own UA is what matters, and a contractor's quote is often sized from a rule of thumb instead:
| UA (BTU/h·°F) | Design load (BTU/h) | ≈ tons |
|---|---|---|
| 200 | 12,168 | 1.0 |
| 300 | 18,252 | 1.5 |
| 400 | 24,336 | 2.0 |
| 500 | 30,420 | 2.5 |
Measure yours
Temsor RightSize reads 12–24 months of your utility bills, fits your real UA with an uncertainty range, and checks the heat pump you were quoted against real cold-climate capacity data. Try the free calculator.
Nearby cities
- Cincinnati, OH (-11 °C design)
- Dayton, OH (-12 °C design)
- Fort Wayne, IN (-14 °C design)
- Louisville, KY (-9 °C design)
Engineering estimate, not a stamped Manual J / permit document. Method validated on simulated homes. See the disclaimer.