RightSize by Temsor

United States · design temperature

Heat pump sizing in Indianapolis, IN

−13 °C(9 °F) design temperature

Try the free calculator

Design temperature used for Indianapolis, IN: -13 °C (9 °F) — the 99 % annual heating design temperature, from 10 years of reanalysis weather. Treat it as ±1 °C: your street can be colder or milder than the grid cell.

What that means for load

Design heat load = your home's heat-loss coefficient (UA) × (70 °F − 9 °F). Illustrative only — your own UA is what matters, and a contractor's quote is often sized from a rule of thumb instead:

UA (BTU/h·°F)Design load (BTU/h)≈ tons
20012,1681.0
30018,2521.5
40024,3362.0
50030,4202.5

Measure yours

Temsor RightSize reads 12–24 months of your utility bills, fits your real UA with an uncertainty range, and checks the heat pump you were quoted against real cold-climate capacity data. Try the free calculator.