Heat pump sizing in Portland, ME
−12 °C(11 °F) design temperature
Design temperature used for Portland, ME: -12 °C (11 °F) — the 99 % annual heating design temperature, from 10 years of reanalysis weather. Treat it as ±1 °C: your street can be colder or milder than the grid cell.
What that means for load
Design heat load = your home's heat-loss coefficient (UA) × (70 °F − 11 °F). Illustrative only — your own UA is what matters, and a contractor's quote is often sized from a rule of thumb instead:
| UA (BTU/h·°F) | Design load (BTU/h) | ≈ tons |
|---|---|---|
| 200 | 11,772 | 1.0 |
| 300 | 17,658 | 1.5 |
| 400 | 23,544 | 2.0 |
| 500 | 29,430 | 2.5 |
Measure yours
Temsor RightSize reads 12–24 months of your utility bills, fits your real UA with an uncertainty range, and checks the heat pump you were quoted against real cold-climate capacity data. Try the free calculator.