Heat pump sizing in Boise, ID
−10 °C(14 °F) design temperature
Design temperature used for Boise, ID: -10 °C (14 °F) — the 99 % annual heating design temperature, from 10 years of reanalysis weather. Treat it as ±1 °C: your street can be colder or milder than the grid cell.
What that means for load
Design heat load = your home's heat-loss coefficient (UA) × (70 °F − 14 °F). Illustrative only — your own UA is what matters, and a contractor's quote is often sized from a rule of thumb instead:
| UA (BTU/h·°F) | Design load (BTU/h) | ≈ tons |
|---|---|---|
| 200 | 11,124 | 0.9 |
| 300 | 16,686 | 1.4 |
| 400 | 22,248 | 1.9 |
| 500 | 27,810 | 2.3 |
Measure yours
Temsor RightSize reads 12–24 months of your utility bills, fits your real UA with an uncertainty range, and checks the heat pump you were quoted against real cold-climate capacity data. Try the free calculator.
Nearby cities
- Spokane, WA (-11 °C design)
- Salt Lake City, UT (-10 °C design)
- Helena, MT (-21 °C design)
- Reno, NV (-10 °C design)
Engineering estimate, not a stamped Manual J / permit document. Method validated on simulated homes. See the disclaimer.