United States · design temperature
Heat pump sizing in Helena, MT
−21 °C(-6 °F) design temperature
Design temperature used for Helena, MT: -21 °C (-6 °F) — the 99 % annual heating design temperature, from 10 years of reanalysis weather. Treat it as ±1 °C: your street can be colder or milder than the grid cell.
What that means for load
Design heat load = your home's heat-loss coefficient (UA) × (70 °F − -6 °F). Illustrative only — your own UA is what matters, and a contractor's quote is often sized from a rule of thumb instead:
| UA (BTU/h·°F) | Design load (BTU/h) | ≈ tons |
|---|---|---|
| 200 | 15,156 | 1.3 |
| 300 | 22,734 | 1.9 |
| 400 | 30,312 | 2.5 |
| 500 | 37,890 | 3.2 |
Measure yours
Temsor RightSize reads 12–24 months of your utility bills, fits your real UA with an uncertainty range, and checks the heat pump you were quoted against real cold-climate capacity data. Try the free calculator.