United States · design temperature
Heat pump sizing in Burlington, VT
−18 °C(0 °F) design temperature
Design temperature used for Burlington, VT: -18 °C (0 °F) — the 99 % annual heating design temperature, from 10 years of reanalysis weather. Treat it as ±1 °C: your street can be colder or milder than the grid cell.
What that means for load
Design heat load = your home's heat-loss coefficient (UA) × (70 °F − 0 °F). Illustrative only — your own UA is what matters, and a contractor's quote is often sized from a rule of thumb instead:
| UA (BTU/h·°F) | Design load (BTU/h) | ≈ tons |
|---|---|---|
| 200 | 13,996 | 1.2 |
| 300 | 20,994 | 1.7 |
| 400 | 27,992 | 2.3 |
| 500 | 34,990 | 2.9 |
Measure yours
Temsor RightSize reads 12–24 months of your utility bills, fits your real UA with an uncertainty range, and checks the heat pump you were quoted against real cold-climate capacity data. Try the free calculator.
Nearby cities
- Albany, NY (-14 °C design)
- Portland, ME (-12 °C design)
- Worcester, MA (-12 °C design)
- Boston, MA (-10 °C design)
Engineering estimate, not a stamped Manual J / permit document. Method validated on simulated homes. See the disclaimer.