Heat pump sizing in Minneapolis, MN
−22 °C(-7 °F) design temperature
Design temperature used for Minneapolis, MN: -22 °C (-7 °F) — the 99 % annual heating design temperature, from 10 years of reanalysis weather. Treat it as ±1 °C: your street can be colder or milder than the grid cell.
What that means for load
Design heat load = your home's heat-loss coefficient (UA) × (70 °F − -7 °F). Illustrative only — your own UA is what matters, and a contractor's quote is often sized from a rule of thumb instead:
| UA (BTU/h·°F) | Design load (BTU/h) | ≈ tons |
|---|---|---|
| 200 | 15,336 | 1.3 |
| 300 | 23,004 | 1.9 |
| 400 | 30,672 | 2.6 |
| 500 | 38,340 | 3.2 |
Measure yours
Temsor RightSize reads 12–24 months of your utility bills, fits your real UA with an uncertainty range, and checks the heat pump you were quoted against real cold-climate capacity data. Try the free calculator.